How the Forward Limit functions is determined by the following Control Parameter:
Forward Limit Format (CP-37)
Use the Forward Limit Format (CP-37) parameter to determine how the
Forward Limit will function during “Run”. If you set CP-37 to "1", then
the M–Traverse will engage “F-Stop” when the Forward Limit is encoun-
tered during “Run”. However, if you want the M–Traverse to terminate
the Constant Pitch Plateau, decelerate to zero speed, process the
Forward End Dwell and then begin the reverse profile back to “Home”
when the Forward Limit is encountered, then set CP-37 to "2".
Table 3-20 Default Polarity Control Parameters
CP Parameter Name Parameter Value
CP-37 Forward Limit Format 1
Table 3-21 Entering Polarity Control Parameters
CP Parameter Name Parameter Value
CP-37 Foward Limit Format Enter “1” to engage ”F-Stop”.
Enter “2” to terminate the
Constant Pitch Plateau,
decelerate to zero, process
the dwell and begin the
reverse profile.