Unload has the fourth highest operating priority. Only from Run, H-Stop, Load, or F-Stop states, but not
from Direct Setpoint Application. Normal operation is from H-Stop with the dancer loaded. If Unload is
requested from Run, the roll(s) ramp to zero speed before starting the Unload sequence below. Unload has a
ten second (10s) timer. If the Dancer is not unloaded within 10 seconds after the Unload input is latched, the
CX-1102 automatically reverts to the F-Stop operating state. The Unload input may be held open to keep the
CX-1102 from changing to F-Stop and therefore complete the Unload.
To activate Unload:
Activate High (Open), Level Sensitive, Latched
Use momentary contact - does not need to be maintained to remain active
Figure 33 Unload Input
Unload
1
F-Stp
Unload
Commo
n
Open Momentarily
F-Stop
2
3