Contrex MLP-Drive Manual do Utilizador Página 96

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 95
3 - 58
Logic Inputs
F–Stop has priority over the other operating states. F–Stop brings the MLP–Drive's
drive output to an immediate Zero.
To activate F–Stop:
Open the F–Stop Input. (F–Stop is latched and does not need to be
maintained to remain active.)
F-STOP
COMMON
Open Momentarily
F-STOP
7
8
J5
R–Stop has the second highest operating priority. R–Stop decelerates the drive output
to Zero, using the Deceleration Time (CP-17).
To activate R–Stop:
Short the F–Stop input to common.
Open the R–Stop input. (R–Stop is latched and does not need to be
maintained to remain active.)
R-STOP
6
F-STOP
7
8
J5
R-STOP
F-STOP
COMMON
Open Momentarily
Vista de página 95